Model |
|
2L-LIC-D/P (Resistance Input) |
|
Input Voltage |
|
AC 220V (100V separate order) |
|
Contact Point Capacity |
|
CONTROL AC 220V 5A
HI/LO AC 220V 3A |
|
Feature |
|
Resistance Input Method(0~300Ω) |
|
Function |
|
Indication , water supply/draining automation and alarm for high/low water level in various kind of tank |
|
Panel CUT |
|
92×45 / 98×50×102 |
|
Material |
|
- HEAD - Nylon Fiber
- FLOAT- P/P foaming
- PIPE - SUS 304 | |
|
Model |
|
2L-LIC-D/P (Current Input) |
|
Input Voltage |
|
AC 220V (100V separate order) |
|
Contact Point Capacity |
|
CONTROL AC 220V 5A
HI/LO AC 220V 3A |
|
Feature |
|
Current Input (4~20mA) |
|
Function |
|
Indication , water supply/draining automation and alarm for high/low water level in various kind of tank |
|
Panel CUT |
|
92×45 / 98×50×102 |
|
Material |
|
- HEAD - Nylon Fiber
- FLOAT- P/P foaming
- PIPE - SUS 304 | |
|
|
|
▶ |
2L-LIC-D/P is the Digital Level Indicating Controller built in a Micom Chip, it can check the indicating value as setting High/Low level alarm and Auto Feeding/Drainage for various kinds of tanks as Digital Mode. It is the Resistance Input (0~300Ω) Type of level controller built in the function isolating a contact output in case of the line disconnecting or the abnormal condition of sensor. |
▶ |
Composed easy to control and set-up, it is manufactured to operate strongly against the power noise or the induction of sensor line, etc. | | |
|
(Resistance Input) |
Using power : AC 220V 60HZ 2W (Special order - 100V) |
Contact Capacity : 5A MAX(LO-AL/HI-AL/Feeding. Drainage Contact) |
Control Output : Contact of Feeding. Drainage, LO-AL, HI-AL, 4/20mA) |
Input Signal : 0-300Ω Resistance(Indicating Meter Sensor & Parallel mode) |
Error : ±0.5FS |
Operating condition : 0~50℃ 0~80%RH |
Outer dimension : 98×50×102(H×W×D) CUT/92×45 |
Usage : Level indicating Controller for various kinds of Water tanks, Oil tank, etc Sensor is required to use with less than 80℃ (Separate order for more than 80℃) | |
MODE |
When pressing a Mode upon setting up, LED Lamp lights in order;LO-AL>START>STOP>HI-AL |
Indicating Limit |
0%~120% (In case of more than 120%, 'hid' flickers) (0%~100%) |
DN |
Using to decrease the setting value in the position of LED Lamp required |
hid |
In case of line disconnecting, the abnormal condition of sensor or 100% setting is not exact, it flickers |
UP |
Using to increase the setting value in the position of LED Lamp required |
Setting limit |
0%~120% (LO-AL/HI-AL/START/STOP) |
ENT |
After setting values in the setting position of each Mode, press an ENT. All are remembered. |
Sensor Input |
Voltage mode 0~1.5V (Indicating meter) by a Resistance Input(0~300Ω) |
Reference |
If not press an ENT for 5 sec., it returns to the original display position |
With the first delivery, LO-AL(40%), START(60%), STOP(80%), HI-AL(90%) are set |
When 'hid' flickers, the function of mode won't work. | |
Reference |
Indicating meter can be connected up to 3 units by Parallel Mode with a Sensor terminal (0~1.5V) |
4~20mA Output Terminal builds in a card (Option) when ordering. (Separate setting or insert is possible) |
Set 100% numeric value as putting a sensor float in 100% position and adjusting 100% set in a unit. | | |
|
|
|
▶ |
2L-LIC-D/P is the Digital Level Indicating Controller built in a Micom Chip, it can check the indicating value as setting High/Low level Alarm and Auto Feeding/Drainage for various kinds of tanks as Digital Mode. It is the Current Input (4-20MA) Type of Level Controller built in the function isolating contact output in case of line disconnecting, short or the abnormal condition of sensor. |
▶ |
Composed easy to control and set-up, it is manufactured to operate strongly against the power noise or the induction of sensor line, etc | | |
|
(Current Input) |
Using power : AC 220V 60HZ 2W (Special order - 100V) |
Contact Capacity : 5A MAX(LO-AL/HI-AL/Feeding. Drainage Contact) |
Control Output : Contact of Feeding. Drainage, LO-AL, HI-AL) |
Input Signal : 4-20MA (Indicating Meter & Sensor Series mode) |
Error : ±0.5FS |
Operating condition : 0~50℃ 0~80%RH |
Outer dimension : 98×50×102(H×W×D) CUT/92×45 |
Usage : Level indicating Controller for various kinds of Water tanks, Oil tank, etc Sensor is required to use with less than 80℃ (Separate order for more than 80℃) | | |
MODE |
When pressing a Mode upon setting up, LED Lamp lights in order;LO-AL>START>STOP>HI-AL |
Indicating Limit |
-3% - 120% (In case of less than -3%, 'oPn' flickers, more than 120%, 'hid' flickers) (0%~100%) |
DN |
Using to decrease the setting value in the position of LED Lamp required |
hid |
In case of more than 120%(more than 20mA, or the abnormal of sensor), it flickers |
oPn |
It flickers in -3% (Less than 4mA or the abnormal of sensor). (When sensor isn't connected) |
UP |
Using to increase the setting value in the position of LED Lamp required |
Setting limit |
0%~120% (LO-AL/HI-AL/START/STOP) |
ENT |
After setting values in the setting position of each Mode, press an ENT. All are remembered. |
Sensor Input |
Current mode (Indicating meter 4~20mA series mode) by Current Input(4~20mA) |
Reference |
If not press an ENT for 5 sec., it returns to the original display position |
With the first delivery, LO-AL(40%), START(60%), STOP(80%), HI-AL(90%) are set |
When 'hid' flickers, the function of mode won't work. | |
Reference |
Indicating meter for 4~20mA use should be connected with a sensor by Series Mode (Line Resistance 700ΩMAX) |
|
Regulate 0~100%, adjusting SPAN and ZERO inside of a Sensor Head | | |
|
|
▶ |
Fill the existence of pressure such as non-pressure tank, pressure tank(less than 5 kg) according to the classes of tanks and separate entry is required if temperature is high (more than 80℃). (Special order in case of more than 5K) |
▶ |
There are two types; Flange and Screw type. In case of a Flange type, it should use with 3″(80Φ)4″(100Φ), In case of a Screw type, 2″(50Φ) socket should be welded to a tank. |
▶ |
Separate order is required for special chemicals and high temperature use. (80℃ and more) | |
Gear-type Sensor |
Flexible Sensor |
◆ |
As Gear-type sensor hasn't the height of ceiling, it is ordered and manufactured as a Gear-type when sensor isn't able to put in a tank. |
◆ |
Refer to the Gear-Type in the tail of 35~36 page |
◆ |
Temperature should be less than 80℃ only (Oil, Water, etc) |
◆ |
Special order is required for the chemicals tank such Hydrochloric acid, Sulphuric acid |
|
[Attention!] Never use to a Pressure tank | |
◆ |
As Flexible-type sensor hasn't the height of ceiling, it is ordered and manufactured as a Flexible-type when sensor isn't able to put in a tank. |
◆ |
In the lower part of sensor, the stain weight is an one-touch fitting. Simple to put a hose in (50mm/m socket-type). |
◆ |
When handling a sensor, Put a stain weight in first and continue to put with care while remaining a sensor as the original position. (Be careful not to be bent) |
◆ |
When delivering, deliver as a fixed position to the handling frame (PVC Pipe) and Do not give an impulse or throw. (It can be the reason of damage) |
◆ |
Temperature should be less than 80℃ only (Oil, Water, etc) |
|
[Attention!] Never use to a Pressure tank | | |
|
■ Indicator/ Automatic water supply and drain/ Low water level Alarm for various water/oil tanks
■ 2 Line Parallel Method (Sensor and Indicator Meter) 4~20mA
※ Caution : Cannot use for oil, chemicals or steam tank (over 80℃)
※ Separate Order for High Temperature and Special Purpose.
Name |
LEVEL INDICATING CONTROLLER |
Model |
2L-LIC-D/P |
Input Voltage |
AC 220V (100V separate order) |
Contact Point Capacity |
CONTROL AC 220V 5A
HI/LO AC 220V 3A |
Input |
input current (4~20mA) |
Function |
Indication , water supply/draining automation and alarm for high/low water level in various kind of tank |
Panel CUT |
92×45 / 98×50×102 |
|